Application
The climate chamber (also known as a temperature and humidity test chamber) provides a wide range of temperature and humidity control. It is used to simulate severely hot, low-temperature, or humid heat environments. Customers can select appropriate models based on performance and test area capacity. It is widely used across various industries such as electronic instruments and meters, new materials, electricians, vehicles, metals, electronic products, and aerospace materials—materials that may encounter environmental conditions during transport, storage, and use.
Features
Cabinet Construction
- Inner cabinet material: Made of SUS304# stainless steel sheet (1.0 mm thick), offering advantages such as acid resistance, corrosion resistance, and ease of cleaning.
- Outer cabinet material: Baked enamel-coated cold-rolled steel sheet, 1.0 mm thick (cabinet in dark gray, door in sky blue).
- Door handle: Features a non-reactive, explosion-proof door handle, providing simple operation, safety, and reliability.
- Insulation system: The insulation zone is filled with polyurethane foam; the connections between the inner and outer chambers use non-metallic materials resistant to high and low temperatures, thereby effectively reducing heat transfer; the door gasket is made of high-quality silicone rubber, which does not age or harden under high or low temperature conditions, providing more reliable sealing; a separate humidification system is used.
- Mobility and positioning system: High-quality lockable PU casters are mounted on the base of the unit, allowing the unit to be easily moved to the designated position and then locked in place.
- Sample shelves: Made of SUS304 stainless steel, perforated and bent into a mesh structure for ease of use; the spacing between shelves is adjustable. Two shelves are provided as standard; samples should be evenly distributed and the load capacity should be ≥20 kg.
- Test port: A Φ100 mm test port is provided, together with the relevant thermal insulation hardware and a special soft sealing plug.
- Observation window: Made of double-layer vacuum tempered glass, with a laminated conductive film inside for defrosting, providing a clear view of the testing process.
Refrigeration System
- The refrigeration units are equipped with French Tecumseh or American Copeland compressors and use environmentally friendly DuPont refrigerant (R404a/R23). They feature a dual-circuit low-temperature system design (–40°C for single-unit operation, –60°C to –70°C for dual-unit cascade operation), which facilitates the use of different compressors at different temperature ranges, thereby improving equipment performance and reducing power consumption.
- Temperature and humidity control uses a P.I.D. + S.S.R. system providing coordinated control through the same channel. It features an automatic calculation function that instantly corrects changes in temperature and humidity conditions, thereby achieving more precise and stable control.
- Both temperature and humidity are controlled by special high-precision controllers, ensuring accurate adjustment and display of relative temperature and humidity. Temperature resolution reaches 0.01°C, while humidity resolution reaches 0.1% R.H.
Heating and Humidification System
- Heating uses high-speed nickel-chromium alloy heating wires.
- A fully independent high-temperature system.
- Humidification uses high-speed nickel-chromium alloy heating wires and stainless steel pipes containing high-temperature magnesium oxide powder, thereby ensuring fast response and long service life.
- The heating and humidification systems are fully independent; the water tank is equipped with a manual water refilling device and an automatic water refilling device.
Control System
- Includes a 7-inch precision LCD programmable temperature controller.
- Smart digital PID microprocessor-based temperature control device.
- Touch screen setting, digital and direct display; humidity is shown directly as a percentage; temperature sensors use PT100 platinum resistance thermometers.
- Temperature control uses the thermal balance adjustment method.
- The precision LCD programmable temperature controller enables program testing; supports multi-group and multi-stage programming operations; there is an option to select fixed values or programs and the ability to set times as needed.
- The equipment's main electrical components, such as circuit breakers and AC contactors, are all of the 'Chint' brand; other electrical accessories are from well-known domestic brands.
- Practical data processing: capable of communicating with a computer via RS-232 interface, equipped with a USB data transfer port (for USB flash drives), enabling display and remote control of temperature, humidity and time curves via computer; thus ensuring reliable storage and retrieval of test process data.
Protection Systems
System-wide protection against overheating, overload of the cooling system, overpressure in the cooling unit, system-wide timing functions, and automatic shutdown after fault alarms.
Standard Features
Capacity and Material
| Internal dimensions (W×D×H) | 500 mm × 600 mm × 500 mm (150L) |
| External dimensions (W×D×H) | 780 mm × 1540 mm × 1420 mm |
| Weight | 250 kg |
| Interior material | SUS #304 stainless steel, 1.0 mm thick |
| Exterior material | Cold-rolled steel sheet, 1.0 mm thick, electrostatic powder coating |
| Insulation material | 100 mm rigid polyurethane foam |
Temperature
| Temperature range | -40°C ~ +150°C |
| Temperature fluctuation | ±0.1 ~ ±0.5°C |
| Temperature homogeneity | ≤2°C |
| Temperature resolution | 0.01°C |
| Temperature deviation | ±0.5 to ±2°C |
| Temperature rate | Without load, average cooling 1°C/min, average heating 3°C/min |
Humidity
| Humidity range | 20% ~ 98% RH |
| Humidity fluctuation | ±0.5 to ±3% RH |
| Humidity uniformity | 5% RH |
| Humidity resolution | 0.1% RH |
| Humidity deviation | +2/-3 (RH above 75%), ±5 (≤75% RH) |
Power Supply
| Power supply | Single phase, 220V, 50Hz |
| Power | 9 kW |
| Current | 4.5 A |
Test Standard
- IEC6008-2-1 Cold
- IEC6008-2-2 Dry Heat
- IEC60068-2-38 Damp Heat, Cyclic
Cooling System
| Compressor | 1.5 HP imported French Tecumseh hermetic compressor |
| Refrigerant | R404A / R404 |
| Cooling method | Single-stage cooling method |
| Blower | Centrifugal fan with forced circulation |
| Evaporator | Finned tube heat exchanger |
| Condensation method | Air cooling |
| Condenser | Stainless steel brazed plate heat exchanger |
| Drying filter | Removes residual moisture and acidic substances from the refrigerant in the cooling system and filters solid foreign matter, copper shavings, etc. in the system. Maintains the normal operation of the expansion valve and capillary tube, and prevents ice blockage and dirt blockage. |
| Humidification system | Nickel-chrome alloy stainless steel humidifier |
| Heating system | Nickel-chrome alloy stainless steel heater |
| Water supply system | Pre-assembled plastic water tank (rust-proof and corrosion-resistant) |
| Sample tray | 2 pcs SUS #304 stainless steel, nominal load capacity: 30 kg/tray |
| Test hole | 1 hole, diameter 50 mm, for cable routing |
Control System
| Controller | Own-developed brand / UE / Keynes / TATO |
| Screen functions | Direct display of setpoint (SV) and actual (PV) temperature and humidity values; displays program number, stage number, remaining time, cycle count and operating time; program editing and graph curve display; a dedicated program editing screen allowing temperature, humidity and time input for four stages per page; indication of fixed point or program running status; language selection, switching between Chinese and English; 7-inch true color display |
| Program capacity and control functions | Number of available programs: up to 120 sets; each program can consist of 1 to 99 stages; total capacity: 1,200 stages; repeatable commands: each command can be repeated up to 999 times; temperature and humidity gradients can be set via a time schedule; programs can be linked together; program creation is simple through a dialog-based interface; group time signal output control; 9 sets of PID parameter settings; skip and hold functions during program execution; power failure program memory; data collection, export and graphic display functions; automatic PID calculation and fuzzy control functions; screen backlight and its duration are adjustable; screen saver function; program editing functions (copy, link, edit); scheduled start and stop; date and time setting; keypad and screen lock (LOCK); standby graph display and error handling explanations |
| Communication interface | RS-232/485 communication; capability to display graphs and retrieve data; can be used as a monitoring and remote control system |
| Setting method | English interface, touch input |
| Operating mode | Programmed mode / Fixed value mode |
| Setting range | Maximum temperature range: ±5°C |
| Screen resolution | Temperature: 0.01°C; Humidity: 0.1%; Time: 0.1 min |
| Power-off memory function | Power failure recovery mode can be set as follows: Hot start / Cold start / Stop |
| Input | PT100 Class A precision platinum resistance thermometer |
| Storage functions | Comes standard with a 256 MB SD card for saving test data curves; data can be uploaded and downloaded, storage capacity is expandable |
| Software working environment | IBM PC compatible computer, Intel Core i3 or higher CPU, 2 GB or more RAM, Simplified Chinese Windows 7-11 operating system |
Protection System
- Overall equipment overtemperature
- Overall equipment phase loss or phase reversal
- Cooling system overload
- High discharge pressure
- Overall equipment timing/timer function
- Automatic shutdown upon fault alarm